KYORITSU 3005A Digital Insulation Conduction Tester KEW 3005A Japanese Original
• Bargraph to display insulation resistance.
• Displays the value of external AC voltage along with flashing symbol.
• Auto null function to automatically subtract the test lead resistance before displaying the real continuity resistance value.
• Live circuit warning beeper.
• Releasing the test button automatically discharges the charges stored in the circuit under test.
• 200mA continuity measuring current to IEC 61557.
• Minimum 1mA current on insulation tests to IEC 61557.
Insulation Resistance
Test voltage
|
250V/500V/1000V
|
Measuring ranges<br>(Mid-scale value)
|
20MΩ/200MΩ/2000MΩ
|
Output voltage on open circuit
|
Rated test voltage+20%, -0%
|
Nominal current
|
1mA DC min.
|
Output short circuit current
|
1.5 mA DC approx.
|
Accuracy
|
±1.5%rdg±5dgt (20MΩ/200MΩ)
±10%rdg±3dgt (2000MΩ)
|
Continuity Test
Measuring ranges<br>(Mid-scale value)
|
20Ω/200Ω/2000Ω
|
Output voltage on open circuit
|
7 - 12V DC
|
Measuring current
|
200mA DC min.
|
Accuracy
|
±1.5%rdg±5dgt (20Ω)
±1.5%rdg±3dgt (200Ω/2000Ω)
|
AC Voltage
AC voltage range
|
0 - 600V AC
|
Accuracy
|
±5%rdg±3dgt
|
General
Safety Standard
|
IEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61010-2-031 IEC 61557-1/2/4
|
IP Rating
|
IEC 60529-IP54
|
EMC Standard
|
IEC 61326-1
|
Power source
|
R6 (AA) (1.5V) × 8
|
Dimensions
|
167(L) × 185(W) × 89(D)mm
|
Weight
|
970g approx
|
Included Accessories
|
7122B (Test leads) Pouch for test leads
8923 (F500mA/600V fuse) × 2
R6 (AA) × 8, Shoulder Strap
Instruction Manual
|